Instantor Rail-PRO™
Why Instantor Rail-PRO
The Rail System is a quick, easy to install UFH system embedded within the oor screed. It is ideal for use in new builds and extensions where a solid oor construction is to be used.
The rails come with an adhesive strip and are secured into position above the slip membrane/
separating layer by removing the protective backing strip and laying the rail in position. It is recommended that rails are fixed at 1m intervals across the floor with pipe staples used every 500mm (in between rails) and where the pipe turns in any radii exceeding 45° to further secure the pipework to the insulation.
For added fixing integrity, pipe staples can be pushed through eyelets within the rail to ensure an enhanced fix to the insulation. Once the rails are secured in position the underfloor heating pipework can be laid and affixed into the rails. The rail enables UFH circuit pipework to be spaced at a minimum of 150mm centres and UFH connection pipework to be spaced at 50mm centres.
It is recommended that all pipework is pressure tested prior to the laying of the screed. Where a liquid type screed is to be installed the slip membrane/separating layer should be sealed to ensure a watertight base is achieved.
Warranty
Pex-Al-Pex: 50 Years, Pert-Evoh-Pert: 50 Years, Manifold: 5 Years, Mixing Kit: 5 Years, Pump: 5 Years, Whisper Controls: 5 Years
Key Features
Cost Effective
Quick & easy to install
Suitable for use with low temperature heating systems
High Heat Output
Suitable for any floor covering
No increase in floor height as UFH Pipework embedded within Screed
Provides accurate fixing method
Available Options
|
Pipe Types Available |
16mm PEX-AL-PEX 16mm 5-Layer PE-RT/EVOH |
|
Typical Pipe Spacings (mm) |
150mm / 200mm |
Pipework Layout Suitability

Floor Covering Suitability

Seek advice from floor covering manufacturer regarding installation methods prior to installation.
Heat Output
Watts per m² at 150mm Pipe Centres
| Pipe Spacing | 150mm | ||||
| Design Room Temperature | 20°C | ||||
| UFH Pipe Circuit ΔT | 5°C | ||||
| Floor Covering Resistance (TOG) |
Flow Temperature (°C) | ||||
| 30 | 35 | 40 | 45 | 50 | |
| 0.00 | 50 | 84 | 117 | – | – |
| 0.50 | 37 | 61 | 86 | 110 | – |
| 1.00 | – | 44 | 61 | 79 | 96 |
| 1.50 | – | 34 | 47 | 61 | 74 |
| 2.00 | – | – | 40 | 52 | 63 |
| 2.50 | – | – | 37 | 47 | 58 |
| Pipe Spacing | 150mm | ||||
| Design Room Temperature | 20°C | ||||
| UFH Pipe Circuit ΔT | 7°C | ||||
| Floor Covering Resistance (TOG) |
Flow Temperature (°C) | ||||
| 30 | 35 | 40 | 45 | 50 | |
| 0.00 | 44 | 77 | 111 | – | – |
| 0.50 | 32 | 56 | 81 | 105 | – |
| 1.00 | – | 40 | 58 | 75 | 93 |
| 1.50 | – | 31 | 45 | 58 | 72 |
| 2.00 | – | – | 38 | 49 | 61 |
| 2.50 | – | – | 35 | 45 | 56 |